Security systems / | System Access |
Integrated System Access Advisor MASTER
GE Interlogix company for more than thirty years of experience in the development and production of security systems: fire and security alarm systems, access control systems, video surveillance systems. GE Interlogix is represented in 30 countries and is the world leader in security systems, which is part of General Electric Industrial Systems. In the market is GE Interlogix Aritech fire alarm systems and integrated access control system. Equipment for fire alarm and access control systems have all the necessary certificates and found our partners at many facilities.
Overview of Access Control System
Advisor MASTER is an integrated security system that combines the functions of the alarm system, access control systems and automatic control of the building. Integrated System Access Advisor MASTER from the outset was designed as an integrated system and all its components are specifically designed to solve complex security problems. Extensive Programming Access Control System Advisor MASTER make it possible to minimize the costs and realize all your wishes.
With its modular design, System Access Advisor MASTER can be constructed optimally depending on the subject: from the small office to the department stores, banks and industrial enterprises. The modular structure of the access control system is implemented using the system data bus (RS485), which allows you to expand the system.
Security features
Structure
The core of the access control system is a control panel ATS4000. The maximum number of protection zones in the access control system - 256. The board of the control panel has 16 zones for connecting alarm sensors and an additional connector for connecting two 8-zone expanders. The base extension of protection zones in the access control system is a bus RS485, on which the address connected expansion modules. The maximum distance between the remote modules in the access control system is 1.5 km away, and can be further expanded up to 6 km by means of insulators/repeaters. The range of targeted expansion modules includes modules for 4, 8 or 8-32 security zone. The chassis module ATS1201 address access control system is set up to 3 zone expanders ATS1202 (see. Figure), which gives an extension of up to 32 security zones. In addition to the address module access control extension modules are connected to the outputs 16 outputs "open collector", 4 or 8 relays. Thus, the targeted expansion module is a basic element for building security and access control.
Settings |
values |
Zone |
16-256 |
Sections |
16 |
The O |
3-255 |
Users |
50-17833 |
Door |
16-64 |
Events in the alarm log |
250-1000 |
Event Log Access Control |
10-1000 |
Protected zones and types of areas
Each control panel access control system using the expander supports up to 256 security areas. Each zone can be connected to a security loop. Each Zone System Access identifies three states: active, passive and Tampere. The access control system supports up to 67 types of security zones, for example, "Button with fixation." Activation/deactivation of the zone puts or removes the partition is disarmed. It can be used to post guards on duty.
Categories
Access Control System Advisor MASTER includes 16 independent subsystems (partitions). Each security zone can be assigned to any section or several sections. Access Control System Advisor MASTER allows easy arming areas related to common premises (corridors, lobbies, stairs). To this end, the common areas are attributed to multiple sections. When setting all these sections, such zones will automatically stand on guard.
In the integrated access control system Advisor MASTER control all the sections can be carried out with the keyboard or with a reader. When the user brings to the smart card reader, System Access opens the door and removes a section of protection. The following users just open the card door. This simplifies the use of the access control system and reduces the number of false alarms. The user can put the partition on the protection if podneset card to the reader access control three times within 10 seconds.
Community
All the databases are stored directly in the control panel memory. Access Control System Advisor MASTER supports up to 17,000 smart cards. The separation of user rights is implemented in the access control system using alarm groups. Alarm group has a set of rights and attributes such as: the right arm/disarm the partition access control, alarm reset, control sections at certain times, access to the specific menus with the keyboard and more than 20 additional functions. These rights apply to all users of a group of access control systems. The group can be assigned a keyboard or a reader. Various keyboard or readers may have different rights. For example, the keyboard from the group "Assembly" will only be possible to program the access control system, and the keyboard from the group "User" can only manage security functions, but changing the settings and access control will not be available regardless of the user's rights. Such groups in the access control system can be up to 138.
Options SKD
Structure
In the integrated access control system Advisor MASTER control panel, themselves keyboard and readers already support access control functions. Each reader, keyboard or controller module has one door ATS1170 input for connecting the button request outputs and to control the door lock. The controller ATS1170 this output relay for readers and keyboards - "open collector". At presentation to the smart card, or set the PIN code System Access Advisor MASTER, authentication and verification of user rights.
The structure of the access control system Advisor MASTER also includes an intelligent controller 4 doors ATS1250, supports advanced features access control.
Controller ATS125O
ATS1250 Controller Access Control System Advisor MASTER is designed to control and control access through a door 4. The board controller has 4 inputs to connect all readers that support the format Weigand. It may be readers Aritech, readers from other manufacturers or biometric readers. The controller access control system placed 4 relays to control door locks and 16 inputs, which connect the magnetic contacts on doors, buttons query output zone monitoring "The door is open for too long." The magnetic contacts are used for access control functions can be used simultaneously in the alarm system.
When using the local bus to which you can connect another 16 readers, keyboards or modules ATS1170, ATS1250 controller supports up to 20 readers.
go through all 48 doors in the intelligent access control system Advisor MASTER function is controlled by the "Global Anti-passack". In addition, System Access allows you to use "software Anti-pass-back", and then the passage is not prohibited, but is a notification and event log entry. The controller allows you to account for the location of users, supports the "run on card + PIN" authorization of "two cards" and "count users in the region".
The controller stores in memory all databases and can work independently during a power failure to the control panel, access control systems. On a system bus RS485 data ATS4000 control panel, you can connect up to 12 of these controllers (48 intelligent doors).
Office building automation
Integrated System Access Advisor MASTER is designed not only to perform security functions and access control, but also for automatics in the building: air-conditioning, lighting, ventilation on relay level. For this purpose, the system provides a mechanism and event flags makrologiki.
Flag of events - is a logical variable that takes the value " true "or" false "depending on events in the access control system. Such flags can be up to 255 and they can be engaged in various events (system events, able to share, areas, doors). Makrologiki expression - an expression of Boolean algebra, which involved four flag events with different time functions, and the result is the same event flag. In any event flag System Access can enable the physical outputs, and thus can be attributed almost all the events of the physical outputs (relay or "open collector").
Software TITAN
With TITAN software can not only make all settings and access control, load settings remotely to the panel, but also to monitor, manage access control, diagnosing, programming smart cards, manage event logs and maintain graphical floor plans.
Using diagnostic tools, TITAN can not only check the integrity Access Control System Advisor MASTER, event log and databases, but also to measure the resistance on the protection inputs and evaluate the voltage drop and the current in the system bus.
Network
If necessary, access control panel Advisor MASTER can be networked. In one segment of the network, you can combine the 16 panels, and 4 of the segment connected to one computer with software TITAN. With its modular design, the flexibility to configure for the object, simplicity and reliability in operation, System Access Advisor MASTER is widespread in Europe.
|